Why can two comparable drainage systems carry different fire evidence?

Cast iron drainage comes with a declared reaction-to-fire class. Strictly speaking, the standards for plastic drainage don’t require one. So why might different fire evidence apply to two similar systems? Jeremy Douglas, specification director at Brymec, explains where that gap comes from and what specifiers should ask for 

Put two drainage systems on the same drawing: they run up the same stack at the same diameter, with similar joints, on the same project. The material is the only real difference. One delivery arrives with a reaction-to-fire classification and a signed declaration, but the other arrives with neither because the standard it’s made to doesn’t require them. Which one should the specifier trust? And what should they be asking for?

Why the paperwork differs

The difference starts in the product standards. BS EN 877, the standard for cast iron drainage, is a designated standard under the Construction Products Regulations, and reaction to fire is one of the characteristics we declare against it in a Declaration of Performance (DoP).

Plastic soil and waste is a different story. Its standards, such as BS EN 1329-1 for PVC-U and BS EN 1519-1 for HDPE, aren’t designated. That means there’s no requirement for a DoP or for a stated fire class. A missing classification only tells you that the manufacturer wasn’t required to test for it. It tells you nothing about how the pipe will behave in a fire, and that’s the problem.

Cast Iron drainage has its own catch. Plain cast iron is non-combustible and can be classed A1 without testing, but drainage pipe doesn’t leave the factory plain. It’s coated, and it goes together with rubber gaskets and couplings. When we classified our cast iron, we tested it as an assembled system, including the coating, gaskets, coated couplings, and coated brackets. It achieved A1. That’s what the contractor installs, so that’s what the class should describe.

What the fire classification tells you

Reaction to fire describes how a product contributes to a fire once flame reaches it. That’s a separate question from fire resistance. It’s also separate from how a pipe passes through a compartment wall or floor, which is the job of the fire-stopping system.

A BS EN 13501-1 classification has three parts, and each has its own test. The main class, A1 to F, covers how much the product adds to the fire. The smoke rating, s1 to s3, matters because smoke reaches escape routes before flame does, and it’s one of the main causes of death in fires. The droplet rating, d0 to d2, matters because burning droplets from a pipe run can start a fire on the level below and cause harm to people underneath.  Because each part comes from a defined test, a designer can compare like with like and building control can check the claim against a report.

Why assumptions don’t hold any more

After Grenfell, Dame Judith Hackitt’s review made it clear that manufacturers are responsible for ensuring the fire performance of their products is properly tested and reported. The Building Safety Act followed. For higher-risk buildings, the golden thread now requires building information to be stored digitally, kept up to date and held as a single source of truth.

A product claim with no test behind it can’t sit in that record. Picture someone reviewing the building in fifteen years’ time who wasn’t on the original team. They find a pipe with no stated class and have two options: rebuild the case from scratch, or take a guess. A replacement that looks ‘like-for-like’ may not be.

The rules are moving the same way. The government’s Construction Products Reform White Paper, published in February 2026, proposes a general safety requirement for products outside designated standards. This would include plastic drainage. The review also says construction product information must be made available digitally. I expect the gap between cast iron and plastic paperwork to close, and I’d rather we close it ahead of the legislation than after.

What we’ve done at Brymec

We didn’t wait. All four Brymec drainage ranges (Cast Iron, PVC-U, VOX dB12 acoustic and HDPE) have been independently tested and classified to BS EN 13501-1, and each one carries a signed declaration. For Cast Iron, that’s our DoP under EN 877. For the plastic ranges, there’s no designated standard, so strictly speaking, a DoP isn’t the right document. Instead, we issue a voluntary Product Performance Declaration, laid out the same way, so a designer can read cast iron and plastics side by side.

For me, the value is in having done the testing, mostly voluntarily. We go to market knowing exactly what our ratings are, rather than relying on assumptions. We state every class as tested, with the sizes and mounting used, because a classification only applies to the configuration that earned it. For the consultant, that removes the grey areas. while the contractor gets a document ready for the technical submission. And it provides the building owner with a record that will still make sense in the golden thread in future years.

What specifiers should ask for

Whatever the material, ask every supplier for the same three things: the BS EN 13501-1 classification, the configuration it was tested in, and a signed declaration. Where the product standard requires a DoP, ask for the DoP. Where it doesn’t, ask whether the manufacturer has test evidence available, and request the report reference.

Two systems doing the same job on the same stack should be judged on the same evidence. We’ve provided ours, and I’d like specifiers to expect the same from everyone.